Chapter 10
The UPS systems are housed in freestanding, double-front cabinets with safety shields
behind the doors. The UPS systems are available in 50/60 Hz with various output power
ratings. Smaller models within a system may be upgraded in the field to larger models:
Table 10-1. Model Numbers
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
Table 10-2. System Input
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
EATON Powerware
®
Product Specifications
System
Powerware 9315 500
Powerware 9315 500
Powerware 9315 400
Powerware 9315 400
Operating Input
480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)
Voltage
400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)
(Nominal +10/–15%)
"3 Hz of nominal (50 Hz or 60 Hz)
Operating Input
Frequency Range
Operating Input
Battery Charge
Current
125% of full load for overload + battery charge
115% of full load for overload + battery charge
Reduced for Generator
Adjustable, set to 102%
Input Current
10% THD at full load (with input filter option installed)
Harmonic Content
Power Walk-In
Adjustable 3–60 second rectifier ramp-up to full utility load
Power Factor
Minimum 0.85
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Models
500 kVA
400 kVA
400 kVA
300 kVA
Actual load + 25% of full load for battery charge with 0.8 pF
output units
Actual load + 15% of full load for battery charge with 0.9 pF
output units
Notes
60 Hz only
60 Hz only
50/60 Hz only
50/60 Hz only
10−1