Remote Notificaton

8.2 Description of Operation

The Remote Notification option performs three basic functions: Call Answer into Terminal
mode, Call Out to a remote terminal, and Housekeeping. Remote Notification also allows
access to any functions available in the Terminal mode from a remote computer or
terminal.

8.2.1 Call Answer

To use the Call Answer function, the modem is configured to automatically answer by
having the user program the S0 register of the modem to a non-zero number. When the
modem receives a call, the UPS is alerted to wait for a connect signal from the modem.
When the modem answers and finishes handshaking, the UPS acknowledges the modem
connect signal and allows the caller into the Terminal mode (see Chapter 7, Serial
Communication"). In this mode, the user can request four items and perform one
command:
NOTE The brackets ([ ]) in the following steps indicate standard keyboard characters.
A
Display all screens (^B, ^M, ^P). Press and hold [CTRL], then press [A].
A
Display battery test results by pressing and holding [CTRL], then pressing [B].
A
Display meters screen by pressing and holding [CTRL], then pressing [M].
A
Display event history by pressing and holding [CTRL], then pressing [P].
A
Reset Call Out Alarms by pressing and holding [CTRL], then pressing [R].
The Reset Call Out Alarms command causes the UPS to cease Call Out attempts on a
currently active alarm and resets that alarm call. See the following section, Call Out" for
more information.
8−2
EATON Powerware
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®