Serial Communication
Table 7-3 shows which options are available for each port. The sections that follow
describe the configuration settings you can change.
Table 7-3. Available Options for Each Communication Port
Port 1
NOTE
7.4.1 Mode
The operational mode of the port. Each communication port operates in one of the
following modes:
Terminal Mode
System Configuration
Mode
Calibration Mode
Computer Mode
Remote Monitor Mode
Port 1 and Port 2 cannot be in the same mode simultaneously; they must always be
operating in different modes. The modes are described later in this chapter.

7.4.2 Rate

The baud rate of the equipment connected to this port. The baud rate determines the
speed of data transferred between the UPS and the connected equipment. For Remote
Monitor mode, the baud rate must be set to 300. All other modes should operate at the
highest baud rate available with the connected equipment. 300 baud is not recommended
for any mode except Remote Monitor.
You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19,200.
7−6
EATON Powerware
Port 2
Options
X
X
Terminal Mode
X
Calibration Mode
X
X
System Configuration Mode
X
Computer Mode
X
Remote Monitor Mode
X
X
Baud rate of 300, 1200, 2400, 4800, 9600, or 19200
X
X
Data size/stop bits of 8/1 or 8/2
X
Data size/stop bits of 7/1 or 7/2
X
X
Disabled handshaking
X
X
XON/XOFF handshaking
You should only change Port 2 options if field service has performed a wiring change.
System events are logged immediately as they occur.
Allows you to set building alarms, battery tests, etc.
(Check with your sales or service representative for availability.)
Used only by service personnel.
Provides a proprietary Binary Computer Mode (BCM) Interface.
Sends all system event information to an RMP, RIM, or SCM.
Available for Port 1 only.
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®