Using the LOAD OFF Button

12.2 Resetting the UPS System after Load Off

Do not attempt to restart the system after Load Off until the cause of the emergency has been
identified and cleared.
The Load Off PUSH TO RESET button is a small white button on the UPS Control Panel. The
PUSH TO RESET button pops out and the CB1 switch trips when the LOAD OFF button on
the Monitor Panel is activated.
To reset the UPS system:
1. Press the Load Off PUSH TO RESET button until it clicks in and remains recessed.
2. Move the CB1 switch from the center (tripped) position to OFF. The switch should
3. The UPS system is now reset. To restart the UPS system, follow the procedure in
12−2
EATON Powerware
be difficult to move from the TRIPPED position.
Chapter 4, Starting and Stopping the UPS."
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®