Serial Communication
7.5 Terminal Mode
In this mode, system events are continually logged through the serial port to the device
connected to the port. Port 2 operates by default in Terminal mode.
The printed log entries contain a time and date stamp and the alarm text message.
Terminal mode uses this format for printing alarm entries:
An alarm message is prefixed by the word CLEAR" whenever an alarm is entered into the
Event History Log with a cleared status.
7.5.1 Printing Selected Information
If a port is operating in Terminal mode and is connected to a computer, you can use key
combinations at any time to print only selected information:
[Ctrl]+[P]
[Ctrl]+[M]
[Ctrl]+[A]
[Ctrl]+[B]
To use a key combination, hold down the Control key and press the letter key.
7−8
EATON Powerware
MMM DD
HH:MM:SS.hh
Symbol
Description
MMM
Month (3 letters)
DD
Day (2 digits)
HH
Hour (2 digits)
MM
Minute (2 digits)
SS
Second (2 digits)
hh
Hundredths of Second (2 digits)
KYWD
Keyword (ALARM, NOTICE, COMMAND, or STATUS)
::::
System Diagnostic Information
<CR>
Carriage Return Character (ASCII 13)
<LF>
Line Feed (ASCII 10)
Prints the entire log with a header
Prints the current system meters with a header
Prints all system information
Prints Battery Test Log
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®
::::
KYWD MESSAGE
<CR> <LF>