300–500 kva
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Product Specifications
Table 10-3. System Output
Rectifier/Charger Capacity
DC Filtering
UPS Output Capacity
Output Voltage Regulation
Output Voltage Adjustment
(Nominal +/–5%)
Output Voltage Harmonic Content
Output Voltage Balance
Output Voltage Phase
Displacement
Output Transients
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Overload Capability
Maximum Output Capability
Table 10-4. Environmental Specifications
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD)
Immunity
10−2
EATON Powerware
125%
Ripple voltage less than 0.5% peak to peak
100% rated current
1% (10% to 100% load)
480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)
400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)
3% max THD, 2% max single (linear load)
3% for 100% maximum load imbalance
3° for 100% maximum load imbalance
"5% for 100% load step or removal
"0.01 Hz free running
Bypass within voltage limits of +5%, –8% of output setting; bypass within
±0.5 Hz
1 Hz per second maximum (adjustable)
125% for 10 minutes
150% for 10 seconds
300% peak for 10 cycles without bypass
0 to 40°C without derating. However, operating at or near 40°C will
adversely affect battery life (refer to your battery specifications for more
information). The recommended operating temperature is 25°C.
Maximum 1500m (5000 ft) at 40°C without derating
–20 to +70°C (prolonged storage above 40°C will cause rapid battery
self-discharge)
95% maximum noncondensing
75 dBA at a 1m distance
Meets FCC Regulation 47, Part 15, Subpart J, for class A devices
Meets IEC 801-2 specifications. Withstands up to 25 kV without damage and
with no disturbance or adverse effect to the critical load.
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®