Battery Mode; Figure 3-3. Path Of Current Through The Ups In Battery Mode - Eaton Powerware 9315 Operation Manual

300–500 kva
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Understanding UPS Operation

3.3 Battery Mode

The UPS transfers to Battery mode automatically if a utility power outage occurs, or if the
utility power does not conform to specified parameters. In Battery mode, the battery
provides emergency DC power that the inverter converts to AC power. When the UPS
switches to Battery mode, the alarm indications depend on the cause and condition of the
battery charge. The length of time the system can operate in Battery mode depends on
loading and the battery supply capacity.
Figure 3-3 shows the path of electrical power through the UPS when operating in Battery
mode.
Bypass
Input
Rectifier
Input
Path of electrical power
When the discharging battery voltage reaches the lower limit of UPS operation capability,
the critical load transfers to Bypass mode if it is available. If Bypass input is not available, a
Shutdown Imminent" warning occurs. The warning time before critical load loss occurs is
approximately two minutes, depending on battery capacity and the amount of loading.
If incoming power returns to within specified parameters, the UPS automatically returns to
Normal mode and alarm indications clear. However, the process of returning to Normal
mode is not instantaneous. The rectifier gradually draws increasing power from the
incoming utility until Normal mode is achieved.
3−4
EATON Powerware
Rectifier
CB1

Figure 3-3. Path of Current Through the UPS in Battery Mode

9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®
Bypass
K4
Inverter
Battery
K3
(Open)
Transformer
Output

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents