Sensor Battery Status Test and Low Battery Power Notification

Table 7.
Battery status: LED5 on the sensor
User action
LED display
Press Test
Solid green for 5 seconds
button (S5)
Solid red for 5 seconds
No light
None
Blinking red: 1-blink pattern
Cycle repeats every 15 minutes.
i
Blink pattern is On for 1/4 s, Off for 3/4 s, with 2 s Off between repetitions [Bryan: please verify about the 2 s Off. Thank you PK].

24 V Power Status

34
Operation, Maintenance, and Troubleshooting
LED5 indicates battery status. LED5 is:
Located on the sensor
Bi-color (green/red)
Normally Off
Testing is initiated by pressing the Test button (S5). When the battery power goes
below a certain threshold, LED5 is automatically activated.
Table 7
explains how to interpret LED5 on the sensor.
i
repeated 5 times.
On the receiver
(Figure 11, p.
24 V power is normal.
Indicates...
Battery condition is adequate for proper operation.
Battery condition is low. Batteries should be replaced.
Batteries are totally dead or not installed properly, or
sensor is defective.
Battery condition is low. Approximately 14 days of
operation remain before the battery is too weak to power
the sensor.
25), LED5 will light and stay constantly On when