Occupied (On)/Unoccupied (Cancel) Button Operation - Trane WZS Installation & Operation Manual

Wireless zone sensor
Table of Contents

Advertisement

Occupied (On)/Unoccupied (Cancel) Button Operation

Table 8.
Occupied and Unoccupied button functions
User input at sensor
User presses Occupied button
(occupancy request)
User presses Unoccupied
button (cancels occupancy
request)
User presses Unoccupied
button (Comm5 Service pin
i , ii
request)
i
Consult the appropriate unit control module literature for information about this function.
ii
Comm5 is Trane's implementation of LonTalk
BAS-SVX04A-EN • Wireless Zone Sensor
Operation, Maintenance, and Troubleshooting
The Wireless Zone Sensor set supports Occupied (On) and Unoccupied (Cancel)
buttons for timed override request and Service pin request (see
Figure 19
for button locations.
Note: Not all systems support the timed override Occupied and Unoccupied
functions.
User pushes button for... Output generated at receiver
0.2 to 6 seconds
0.2 to 6 seconds
10 to 25 seconds
®
.
Figure 19. Sensor: Location of Occupied button, Unoccupied button, and star (*)
and double star (**) on thumb wheel
Space temperature output is
driven to 10 Ω (nominal)
Space temperature output is
driven to 1330 Ω (nominal)
Space temperature output is
driven to 10 Ω (nominal)
** on thumb wheel
(* is hidden from view)
Occupied button
Unoccupied button
Table
8). See
Output will generate for...
4 seconds
4 seconds
15 seconds
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents