Preparation
• Start signal.................................. Switch, relay, etc. (for 1)
• Frequency setting signal............. 0 to 5V, 0 to 10V or 4 to 20mA DC signals from a potentiometer or
• Operation unit ............................. Operation panel (FR-DU04), parameter unit (FR-PU04)
• Connection cable........................ To be prepared for use of the operation unit away from the inverter
3) Combined operation mode
Change the setting of Pr. 79 "operation mode selection" as follows:
Setting
Running frequency setting
PU (FR-DU04/FR-PU04)
3
•Direct setting and
setting, Multi-speed setting
Terminal signal
•0 to 5VDC across 2-5
•0 to 10VDC across 2-5
4
•4 to 20mADC across 4-5
•Multi-speed selection (Pr. 4 to Pr. 6, Pr. 24
to Pr. 27, Pr. 232 to Pr. 239)
•Jog frequency (Pr. 15)
(4) Communication operation mode
Communication operation can be performed by connecting a personal computer and the PU connector with
the RS-485 communication cable.
The inverter setup software (FR-SW -SETUP-WE (or - WJ for Japanese Version)) is available as a start-up
support software package for the FR-A500.
Preparation
• Connection cable........................ Connectors and cables available on the market
• For the operation enviroment of inverter setup software, refer to the instruction manual of the inverter
setup software.
outside the inverter (for 2)
FR-CB2
(option) or the following connector and cable available on the
market:
Connector
: RJ45 connector
Cable
: Cable conforming to EIA568 (e.g. 10BASE-T cable)
Description
Terminal signal
•STF
/
key
•STR
Parameter unit
key
FWD
key
REV
•Connector ........................... : RJ45 connector
•Cable .................................. : Cable conforming to EIA568
49
OPERATION/CONTROL
Start signal
(e.g. 10BASE-T cable)
3