Mitsubishi Electric FR-A500 Instruction Manual page 239

Transistorized inverter
Hide thumbs Also See for FR-A500:
Table of Contents

Advertisement

<When used with communication options >
About of the setting values "10, 12, 20, 22" to Pr. 340 "link startup mode selection"
1) Switching between the PU operation mode and network operation mode is enabled.
When Pr.340="10 or 12" and Pr.79="0 or 6", operation can be switched between the PU operation and
network operation from the operation panel (FR-DU04) or parameter unit (FR-PU04).
• FR-DU04
Shifts to the PU operation mode when
shifts to the network operation when
• FR-PU04
Shifts to the PU operation mode when the
the
key is pressed.
2) Switching between the external operation mode and network operation mode by the external terminal
(Addition of the setting of "66" to Pr.180 to 186 "input terminal function selection")
When "20 or 22" is set in Pr.340 "link start up mode selection", switching between external operation and
network operation can be performed by the external terminal.
Setting
Signal Name
66
Note: 1. "66" can be set even when the setting values of Pr.340 "link start up mode selection" are other
than "20 and 22" or when a communication option is not connected. However, operation can not
be switched by the X66 signal.
2. For the X66 signal, operation only from the external terminal is valid independently of the setting
of Pr.338 "operation command source", Pr.339 "speed command source" (can not be operated
from the network).
3) Switching between link start up mode and operation mode
The inverter starts up in the network operation mode at power-on.
Pr.340
Operation
Setting
Mode
Pr.79
PU or network
0
operation
1
PU operation
Network
2
operation
External/PU
3
combined
operation
External/PU
4
combined
operation
10,
12(*1)
Programmed
5
operation
6
Switch-over
PU operation
7(*2)
interlock
Operation
mode switch-
8(*2)
over by the
external signal
Signal for switching between external operation and network operation
X66
X66-OFF : external operation mode, X66-ON : network operation mode
Mode at Power On or at Restoration from Instantaneous Power Failure
Inverter operates in the network operation mode.
Operation mode can be switched between the PU operation and the network operation.
Inverter operates in the PU operation mode.
Inverter operates in the network operation mode.
Running frequency is set in the PU operation mode and the start signal is set in the external
operation mode.
Running frequency is set in the external operation mode and the start signal is set in the PU
operation mode.
Inverter operates in the programmed operation mode.
Inverter operates in the network operation mode.
Operation mode can be switched between the PU operation and the network operation.
X12 signal ON
X12 signal OFF
X16 signal ON
X16 signal OFF
is displayed on the operation mode switching menu and
is displayed.
key is pressed and to the network operation mode when
Function
Inverter operates in the external operation mode. (Operation mode can
be switched to the PU operation mode by the parameter unit.)
Inverter operates in the external operation mode.
Inverter operates in the external operation mode.
Inverter operates in the PU operation mode.
230
OPTIONS