Advertisement

To enter the Pr. 92 and Pr. 93 motor constants in [mH]
<Operating procedure>
1. Set any of the following values in Pr. 71:
•Standard motor ....................................................................................... Pr. 71 = "0"
•Constant-torque motor ............................................................................ Pr. 71 = "1"
•Mitsubishi standard motor SF-JR 4 poles (1.5kW (2HP) or less)............ Pr. 71 = "20"
2. Set "801" in Pr. 77.
(Only when the Pr. 80 and Pr. 81 settings are other than "9999", the parameter values of the motor
constants (Pr. 90 to Pr. 94) can be displayed. Though the parameter values of other than Pr. 90 to Pr. 94
can be displayed, they are parameters for manufacturer setting and shall not be changed.)
3. In the parameter setting mode, read the following parameters and set desired values:
The setting value of Pr. 94 can be found by the following calculation.
Pr. 94 setting value = (1 -
Parameter
Number
90
Motor constant R1
91
Motor constant R2
92
Motor constant L1
93
Motor constant L2
94
Motor constant X
4. Return the Pr. 77 setting to the original value.
5. Refer to the following table and set Pr. 84:
Parameter
Number
84
Rated motor frequency
Note: 1. Pr. 90 to Pr. 94 values may be read only when the Pr. 80 and Pr. 81 settings are other than
"9999" (advanced magnetic flux vector control selected).
2. Set "9999" in Pr. 90 to Pr. 94 to use the standard motor constants (including those for the
constant-torque motor).
Pr. 89
Refer to Pr. 80.
2
M
) × 100(%)
L1×L2
Equivalent Circuit Diagram of Motor
R1
I1
M
V
L1= I1 + M: Primary inductance
L2= I2 + M: Secondary inductance
Name
Setting Range
0 to 50 , 9999
0 to 50 , 9999
0 to 1000mH, 9999
0 to 1000mH, 9999
0 to 100%, 9999
Name
Setting Range
50 to 120Hz
I2
R1 : Primary resistance
R2 : Secondary resistance
I1 : Primary leakage inductance
R2/S
I2 : Secondary leakage inductance
M : Excitation inductance
S
: Slip
Setting
Increments
0.001
0.001
0.1mH
0.1mH
0.1%
Setting
Increments
0.01Hz
122
PARAMETERS
Factory
Setting
9999
9999
9999
9999
9999
Factory
Setting
60Hz <50Hz>