Watt-Hour Meter Clear/Actual Operation Hour Meter Clear (Pr. 170, Pr. 171); Input Terminal Function Selection (Pr. 180 To Pr. 186) - Mitsubishi Electric FR-A500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-A500:
Table of Contents

Advertisement

4.2.50 Watt-hour meter clear/actual operation hour meter clear
(Pr. 170, Pr. 171)
Pr. 170 "watt-hour meter clear"
Pr. 171 "actual operation hour meter clear"
You can clear the watt-hour value and actual operation hour monitoring function.
Parameter Number
Setting Range
170
171
<Setting>
Write "0" in the parameters to clear the watt-hour value and actual operation hour.
REMARKS
The watt-hour value is monitored at the Pr. 52 setting of "25", and the actual operation hour at the Pr. 52
setting of "23".
Pr. 173 to Pr. 176

4.2.51 Input terminal function selection (Pr. 180 to Pr. 186)

Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "RT terminal function selection"
Pr. 184 "AU terminal function selection"
Pr. 185 "JOG terminal function selection"
Pr. 186 "CS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter
Terminal
Number
Symbol
180
RL
181
RM
182
RH
183
RT
184
AU
185
JOG
186
CS
Minimum Setting
Increments
0
1
0
----- --
Refer to Pr. 160.
Factory Setting
Factory-Set Terminal Function
0
Low-speed operation command (RL)
1
Middle-speed operation command (RM)
2
High-speed operation command (RH)
3
Second function selection (RT)
4
Current input selection (AU)
5
Jog operation selection (JOG)
Automatic restart after instantaneous
6
power failure selection (CS)
Related parameters
Pr. 52 "DU/PU main display data
selection"
Factory Setting
9999
0
155
PARAMETERS
Setting Range
0 to 99, 9999
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents