Mitsubishi Electric FR-A500 Instruction Manual page 127

Transistorized inverter
Hide thumbs Also See for FR-A500:
Table of Contents

Advertisement

Parameter details
Parameter
Number
9
71 (Note1)
83
84
90
91
92
93
94
96 (Note2)
Note: 1. The electronic overcurrent protection characteristics are also selected simultaneously.
2. Select "101" to increase tuning accuracy.
(2) Tuning execution
• For PU operation, press the
• For external operation, switch on the run command.
Note: 1. When "101" is set in Pr. 96, guard against hazards because the motor rotates.
2. To force tuning to end
• Switch on the MRS or RES signal or press the
• Switch off the tuning start command or make a forced stop.
3. During offline auto tuning, the following I/O signals are only valid:
• Input signals
STOP, OH, MRS, RT, CS, RES, STF, STR
• Output signals
RUN, OL, IPF, FM, AM, A, B, C
4. Special caution should be exercised when a sequence has been designed to open the
mechanical brake with the RUN signal.
5. When executing offline auto tuning, give the run command after switching on the main circuit
power supply (R, S, T <L
Setting
0 to 500A
Set the rated motor current (A).
0
Electronic overcurrent protection thermal characteristics suitable for standard motor
Electronic overcurrent protection thermal characteristics suitable for Mitsubishi
1
constant-torque motor
Electronic overcurrent protection thermal characteristics suitable for standard motor5-
2
point flexible V/F characteristics
Mitsubishi SF-JR4P standard motor (1.5kW (2HP) or less), electronic overcurrent
20
protection thermal characteristics for advanced magnetic flux vector control
3
Standard motor
13
Constant-torque motor
Mitsubishi SF-JR4P standard motor
23
(1.5kW (2HP) or less)
4
Standard motor
14
Constant-torque motor
Mitsubishi SF-JR4P standard motor
24
(1.5kW (2HP) or less)
5
Standard motor
15
Constant-torque motor
6
Standard motor
16
Constant-torque motor
7
Standard motor
17
Constant-torque motor
8
Standard motor
18
Constant-torque motor
0 to 1000V
Set the rated motor voltage (V).
50 to 120HZ
Set the rated motor frequency (Hz).
0 to, 9999
0 to, 9999
0 to, 9999
Tuning data
(Values measured by offline auto tuning are set automatically.)
0 to, 9999
9999
0 to 100%
0
Offline auto tuning is not performed.
1
Offline auto tuning is performed without motor running.
101
Offline auto tuning is performed with motor running.
or
key.
FWD
REV
, L
, L
1
2
Description
STOP
RESET
>) of the inverter.
3
118
PARAMETERS
Select "offline auto tuning setting"
Auto tuning read or change setting
enabled
Star connection
Direct input of
motor constants
enabled
Delta connection
Direct input of
Star connection
motor constants
and offline auto
Delta connection
tuning
key to end.