Reverse Rotation Prevention Selection (Pr. 78) - Mitsubishi Electric FR-A500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-A500:
Table of Contents

Advertisement

4.2.35 Reverse rotation prevention selection (Pr. 78)

Pr. 78 "reverse rotation prevention selection"
This function can prevent any reverse rotation fault resulting from the incorrect input of the start signal.
Used for a machine which runs only in one direction, e.g. fan, pump.
(The setting of this function is valid for the PU, external and communication operations.)
Parameter
Factory
Number
Setting
78
<Setting>
Pr. 78 Setting
0
Both forward and reverse rotations allowed
1
Reverse rotation disallowed
2
Forward rotation disallowed
Setting Range
0
0, 1, 2
Function
Related parameters
Pr. 79 "operation mode selection"