<Operating conditions>
• The motor is connected.
• The motor capacity is equal to or one rank lower than the inverter capacity. (0.4kW or more)
• The maximum frequency is 120Hz.
• Special motors such as high-slip motor and high-speed motor cannot be tuned.
• When "101" (offline auto tuning with motor running) is set in Pr. 96, note the following:
1) Torque may not be enough during tuning.
2) The motor may be run at nearly its rated frequency (Pr. 84 setting) without problem.
3) The brake is open.
4) No external force is applied to rotate the motor.
• If "1" (tuning without motor running) is set in Pr. 96, the motor may run slightly. Therefore, fix the motor
securely with a mechanical brake, or before tuning, make sure that there will be no problem in safety if the
motor runs.
This instruction must be followed especially for vertical lift applications.
Note that if the motor runs slightly, tuning performance is unaffected.
Note: Offline auto tuning will not be performed properly if it is performed when the reactor or surge voltage
suppression filter (FR-ASF-H) is connected between the inverter and motor.
Remove it before starting tuning.
<Setting>
(1) Parameter setting
• Using Pr. 80 and Pr. 81, select the advanced magnetic flux vector control.
• Refer to the parameter details list and set the following parameters:
1) Set "1" or "101" in Pr. 96.
•For setting of "1" ................................................................. Tuning without motor running.
•For setting of "101" ............................................................. Tuning with motor running.
2) Set the rated motor current (A) in Pr. 9.
3) Set the rated motor voltage (V) in Pr. 83.
4) Set the rated motor frequency (Hz) in Pr. 84.
5) Select the motor using Pr. 71.
•Standard motor ....................................................................................... Pr. 71 = "3"
•Constant-torque motor............................................................................ Pr. 71 = "13"
•Mitsubishi standard motor SF-JR 4 poles (1.5kW (2HP) or less) . . . . . Pr. 71 = "23"
Note: 1. Pr. 83 and Pr. 84 are only displayed when the advanced magnetic flux vector control is selected
(Pr. 80, Pr. 81).
2. In these parameters, set the values given on the motor rating plate. When the standard motor has
more than one rated value, set 200V/60Hz or 400V/60Hz.
After tuning is finished, set the Pr. 9 "electronic thermal O/L relay" value to the rated current at the
operating voltage/frequency.
It takes about 25s until
tuning completes.
At this time, exciting noise is
generated.
It takes about 40s until
tuning completes.
The motor rotates at 60Hz.
117