Mitsubishi Electric FR-A500 Instruction Manual page 101

Transistorized inverter
Hide thumbs Also See for FR-A500:
Table of Contents

Advertisement

Note: 1. The monitoring of items marked × cannot be selected.
2. By setting "0" in Pr. 52, the monitoring of "output frequency to alarm display" can be selected in
sequence by the
3. *"Frequency setting to output terminal status" on the PU main monitor are selected by "other
monitor selection" of the parameter unit (FR-PU04).
4. **The load meter is displayed in %, with the current set in Pr. 56 regarded as 100%.
5. The motor torque display is valid only in the advanced magnetic flux vector control mode.
6. The actual operation time displayed by setting "23" in Pr. 52 is calculated using the inverter
operation time. (Inverter stop time is not included.) Set "0" in Pr. 171 to clear it.
7. When Pr. 53 = "0", the level meter display of the parameter unit can be erased.
8. By setting "1, 2, 5, 6, 11, 17 or 18" in Pr. 53, the full-scale value can be set in Pr. 55 or Pr. 56.
9. The cumulative energization time and actual operation time are calculated from 0 to 65535 hours,
then cleared, and recalculated from 0.
When the operation panel (FR-DU04) is used, the display shows "----" after 9999 or more hours
have elapsed. Whether 9999 or more hours have elapsed or not can be confirmed on the
parameter unit (FR-PU04).
10.The actual operation time is not calculated unless the inverter has operated for longer than one
hour continuously.
11. When the operation panel (FR-DU04) is used, the display unit is Hz, V or A only.
12.Position pulse and orientation status function when the FR-A5AP option is used. If the option is
not used, "19" or "22" may be set in Pr. 52 and the value displayed remains "0" and the function is
invalid.
13.The cumulative power is accumulated from 0 to 99999kWh, then cleared, and accumulated again
from 0.
When the operation panel (FR-DU04) is used, the display shows "----" after 9999 or more hours
have elapsed. Whether 9999 or more hours have elapsed or not can be confirmed on the
parameter unit (FR-PU04).
REMARKS
For the monitor set in Pr. 52, its display position depends on the set value.
Factory setting
*The monitor displayed at powering on is the first monitor. Refer to page 52 for the setting method of the
first monitor.
First monitor (It is shown at power-on)
FR-DU04
CONTROL PANEL
MON
EXT
PU
REV
FWD
Output frequency monitor
1) Displayed on the third monitor when the set value is "5 to 14".
First monitor
Output frequency monitor
2) Displayed on the second monitor instead of output current monitor when the set value is "17, 18, 24".
First monitor
Output frequency monitor
3) Displayed on the third monitor instead of output voltage monitor when the set value is "19 to 23, 25".
First monitor
Output frequency monitor
key.
SET
Second monitor
FR-DU04
CONTROL PANEL
Hz
SET
A
V
MON
EXT
REV
Output current monitor
2)
Second monitor
SET
Output current monitor
Second monitor
SET
Set value "17, 18, 24"
monitor
Second monitor
SET
Output current monitor
Third monitor
FR-DU04
Hz
SET
A
V
PU
MON
EXT
FWD
REV
Output voltage monitor
1)
3)
SET
Set value "5 to 14" monitor
SET
Output voltage monitor
SET
Set value "19 to 23, 25"
92
PARAMETERS
Alarm monitor
FR-DU04
With alarm
CONTROL PANEL
Hz
SET
A
V
PU
MON
FWD
Third monitor
Third monitor
Third monitor
monitor
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
SET