4.2.54 Programmed operation function (Pr. 200 to Pr. 231)

Pr. 200 "programmed operation minute/second
selection"
Pr. 201 to Pr. 210 "program set 1 1 to 10"
Pr. 211 to Pr. 220 "program set 2 11 to 20"
Pr. 221 to Pr. 230 "program set 3 21 to 30"
Pr. 231 "timer setting"
In programmed operation, automatic operation is performed under the control of the internal timer in
accordance with the preset time of day, running frequency and rotation direction.
This function is made valid when the following parameter is set to the following value:
•Pr. 79 = "5" (programmed operation)
You can select the time unit for programmed operation between "minute/second" and "hour/minute".
The start time of day, rotation direction and running frequency are defined as one point and every 10 points
are grouped into three:
•Group 1: Pr. 201 to Pr. 210
•Group 2: Pr. 211 to Pr. 220
•Group 3: Pr. 221 to Pr. 230
Use Pr. 231 to set the time of day when programmed operation is started.
Parameter
Factory Setting
Number
200
0
201 to 210
0, 9999, 0
211 to 220
0, 9999, 0
221 to 230
0, 9999, 0
231
0
<Wiring example>
•For sink logic
Setting Range
0 to 3
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999:
Frequency
0 to 99.59: Time
0 to 99.59
Inverter
R,S,T
〈 L
,L
,L
1
2
3
Programmed
STF
operation start
RH
Group selection
RM
Terminal function
RL
STR
Timer reset
Input signal common
SD
161
Related parameters
Pr. 76 "alarm code output selection"
Pr. 79 "operation mode selection"
Remarks
0, 2 [minute/second]
1, 3 [hour/minute]
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
U,V,W
Motor
Pr. 79 = 5