3–14
"A" Group: Standard Functions
Func.
Code
SRW Display
A005 [AT] selection
AT-Slct
A011 O–L input active range
start frequency
O-EXS
A012 O–L input active range
end frequency
O-EXE
A013 O–L input active range
start voltage
O-EX%S
A014 O–L input active range
end voltage
O-EX%E
A015 O–L input start
frequency enable
O-LVL
A016 External frequency
filter time constant
F-SAMP
A016:
External Frequency Filter Time Constant – This filter smooths the analog input signal
for the inverter's output frequency reference.
• A016 sets the filter range n=1 to 16. This is a simple moving average calculation,
where n (number of samples) is variable.
• A016 = 17 is a special value. It configures the inverter to use a moveable deadband
feature. Initially the inverter uses the average of the previous 16 samples. Then, the
deadband is employed for each subsequent average of 16 samples. The deadband
works by ignoring small fluctuations in each new average: less than +0.1Hz or –0.2Hz
change. When a 16-sample average exceeds this deadband, then the inverter applies
that average to the output frequency reference, and it also becomes the new deadband
comparison point for subsequent sample averages.
"A" Function
Name /
Four options, select codes:
00... Select between [O] and
O/OI
[OI] at [AT]
01... [O] + [OI] ([AT] input is
ignored)
02... Select between [O] and
keypad potentiometer
03... Select between [OI] and
keypad potentiometer
The output frequency corre-
sponding to the analog input
range starting point,
0000.0Hz
range is 0.0 to 400.0
The output frequency corre-
sponding to the analog input
range ending point,
0000.0Hz
range is 0.0 to 400.0
The starting point (offset) for
the active analog input range,
range is 0. to 100.
00000%
The ending point (offset) for
the active analog input range,
range is 0. to 100.
00100%
Two options; select codes:
00... Use offset (A011 value)
01... Use 0 Hz
0Hz
One range plus one setting:
01 to 16... Moving average,
where n=1 to 16 (number of
00008
samples for average)
17... Use 16-sample average,
plus deadband +0.1/–0.2Hz.
Run
Mode
Edit
Description
Lo Hi
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
✘ ✔
Defaults
–FE(F)
–FU
Units
(EU)
(USA)
00
00
Hz
0.0
0.0
Hz
0.0
0.0
Hz
0.
0.
%
100.
100.
%
01
01
2.
8.
Sam-
ples