Hitachi SJ2002 Series Instruction Manual page 160

Hide thumbs Also See for SJ2002 Series:
Table of Contents

Advertisement

4–18
Using Intelligent Input Terminals
Set Second Motor and Special-Set Second Motor
If you assign the [SET] or [S-ST] function to an intelligent input terminal, you can select
between two sets of motor parameters. The second parameters store an alternate set of
motor characteristics. Two type of inputs are available:
• Set Second Motor - The inverter can select a different motor only in Stop Mode.
• Special-Set Second Motor - The inverter can select a different motor in either Stop
Mode or Run Mode. The following parameter pairs can be alternately selected during
Run Mode: A020/A220, F002/F202, F003/F203, A042/A242, A043/A243, A061/
A261, A062/A262, A092/A292, A093/A293, A094/A294, A095/A295, A096/A296
When the terminal [SET] or [S-ST] is turned ON, the inverter will use the second set of
parameters to generate the frequency output to the motor. When changing the state of the
[SET] input terminal, the change will not take effect until the inverter is stopped.
When you turn ON the [SET] or [S-ST] input, the inverter operates per the second set of
parameters. When the terminal is turned OFF, the output function returns to the original
settings (first set of motor parameters). Refer to
Motors" on page 4–59
Option
Terminal
Code
Symbol
08
SET
53
S-ST
Valid for inputs:
Required settings:
Notes:
If the terminal state for [SET] is changed while the
inverter is running, the inverter continues using the
current set of parameters until the inverter is
stopped.
You cannot configure the inverter to use [SET] and
[S-ST] terminals at the same time.
for details.
Input
Function Name
State
Set (select) 2nd
ON
Motor Data
OFF
Special-Set (select)
ON
2nd Motor Data
OFF
C001, C002, C003, C004,
C005, C006
(none)
"Configuring the Inverter for Multiple
Description
causes the inverter to use the 2nd set of motor
parameters for generating the frequency output
to motor. The selection of 1st or 2nd motor is
available only in Stop Mode.
causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
causes the inverter to use the 2nd set of motor
parameters for generating the frequency output
to motor. The selection of 1st or 2nd motor is
available in Stop Mode or Run Mode.
causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
Example (requires input configuration—see
page 3–45):
(or S-ST)
L
6
5
4
See I/O specs on page 4–6.
SET
3
2
1
PCS