Analog Input Calculate Function – The inverter can mathematically combine two
input sources into one value. The Calculate function can either add, subtract, or multiply
the two selected sources. This provides the flexibility needed by various applica-
tions.You can use the result for the output frequency setting (use A001=10) or for the
PID Process Variable (PV) input (use A075=03).
Digital operator
Potentiometer
A input
[O] input
select
[OI] input
Network variable F001
Digital operator
Potentiometer
B input
[O] input
select
[OI] input
Network variable F001
"A" Function
Func.
Name /
Code
SRW Display
A141 A input select for
calculate function
CALC Slct1
A142 B input select for
calculate function
CALC Slct2
A143 Calculation symbol
CALC SMBL
Description
Five options:
00 .. Digital operator
01 .. Keypad potentiometer
O
02 .. [O] input
03 .. [OI] input
04 .. Network variable (from
ModBus, CANopen,
DeviceNet, ProfiBus)
Five options:
00 .. Digital operator
01 .. Keypad potentiometer
OI
02 .. [O] input
03 .. [OI] input
04 .. Network variable (from
ModBus, CANopen,
DeviceNet, ProfiBus)
Calculates a value based on the
A input source (A141 selects)
ADD
and the B input source (A142
selects). Three options:
00 .. ADD (A input + B input)
01 .. SUB (A input – B input)
02 .. MUL (A input x B input)
SJ200
Inverter
2
A141
A143
A
• 00 A + B
(result)
• 01 A – B
B
• 02 A x B
A142
Run
Defaults
Mode
–FE(F)
–FU
Edit
(EU)
(USA)
Lo Hi
✘ ✔
02
02
✘ ✔
03
03
✘ ✔
00
00
3–29
"CAL"
Units