Monitoring Trip Events, History, & Conditions
Error
Code
E 1 1
E 2 2
E 1 2
E 1 3
E 1 4
E 1 5
E 2 1
E 2 3
E 3 5
E 6 0
- - -
NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values
are still correct. If the power is turned OFF while the [RS] (Reset) intelligent input
terminal is ON, an EEPROM error will occur when power is restored.
Name
CPU error
External trip
USP
Ground fault
Input over-voltage
Inverter thermal trip
Gate array error
Thermistor
Communications error
Under-voltage (brown-
out) with output shutoff
Cause(s)
A malfunction in the built-in CPU has occurred, so
the inverter trips and turns OFF its output to the
motor.
A signal on an intelligent input terminal configured as
EXT has occurred. The inverter trips and turns OFF
the output to the motor.
When the Unattended Start Protection (USP) is
enabled, an error occurred when power is applied
while a Run signal is present. The inverter trips and
does not go into Run Mode until the error is cleared.
The inverter is protected by the detection of ground
faults between the inverter output and the motor upon
during powerup tests. This feature protects the
inverter, and does not protect humans.
The inverter tests for input over-voltage after the
inverter has been in Stop Mode for 100 seconds. If an
over-voltage condition exists, the inverter enters a
fault state. After the fault is cleared, the inverter can
enter Run Mode again.
When the inverter internal temperature is above the
threshold, the thermal sensor in the inverter module
detects the excessive temperature of the power
devices and trips, turning the inverter output OFF.
An internal inverter error has occurred in communica-
tions between the CPU and gate array IC.
When a thermistor is connected to terminals [6] and
[L] and the inverter has sensed the temperature is too
high, the inverter trips and turns OFF the output.
The inverter's watchdog timer for the communica-
tions network has timed out.
Due to low input voltage, the inverter turns its output
OFF and tries to restart. If it fails to restart, then the
alarm trips to record the under-voltage error event.