On both the X-Pedition 8000 and X-Pedition 8600, slot 0 is labeled "CM" and contains the primary
control module. The CM slot cannot be used for line cards. The primary control module must be
installed in this slot. The CM/1 slot can contain a redundant control module (if you install one) or
can contain a line card. Slots 2 to 7 on the X-Pedition 8000 or slots 2 to 15 on the X-Pedition 8600
can contain any line cards unless otherwise noted in Installing Line Cards
information about these items, see Control Modules
You can install line cards in any order in the slots. For example, you could install line cards in slots
2 and 5 and leave the other line card slots empty. The X-Pedition provides non-blocking throughput
regardless of the software features you are using. Therefore, you do not need to "load balance" line
cards by placing them in certain relationships to balance the load on the backplane. Regardless of
where you install the line cards, the backplane can provide full, non-blocking throughput.
Backplane
The backplane occupies the rear of the chassis and connects the power supplies, control modules,
and line cards together. The power supplies use the backplane to provide power to the rest of the
system. The line cards and control modules use the backplane to exchange control information and
packets. The backplane is installed at the factory. Contact Enterasys Networks if you wish to
replace the backplane.

Fan Module

The X-Pedition contains a fan module to provide a cooling air flow across the control module(s)
and line cards. The fan module is located on the left side of the control modules and line cards. The
X-Pedition 8000 fan module contains two fans; the X-Pedition 8600 fan module contains six fans.
The fan module is installed at the factory, but you can replace the module yourself, if necessary.
Note:
To ensure that the fan module can provide adequate cooling, always provide a minimum of
3 inches of clearance on each side of the chassis.
Hot Swapping a Fan Tray
Note:
Before you hot swap a fan tray on the X-Pedition, have the replacement fan nearby and
ready to install—delays in completing the swap may cause the router to overheat.
1.
Loosen the captive screws.
2.
Remove the fan tray (the fans will wind down and stop). Although the system will continue to
operate normally with the fans removed, if the fans are removed long enough the system will
overheat, power off, and reboot. When the fan tray is removed, the following message will
appear on the console:
%SYS-W-FANFAILED, system fan(s) have failed or fan tray is not installed
12
on page 14
and Line Cards
Enterasys X-Pedition 8000/8600 Getting Started Guide
on page
71. For
on page
20.