Program Mode
Input Channel 1 Function Selection (65)
Factory default for Channel 1 is '0' for activation on fire alarm (2-wire smoke). Enter '1' for pull station; '2' for
normally open contact device; '3' for host panel trouble; '4' for fire supervisory; '5' for fire supervisory autoresetta-
ble; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
Input Channel 2 Function Selection (66)
Factory default for Channel 2 is '1' for pull station. Enter '2' for normally open contact device; '3' for host panel
trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for waterflow silenceable; '7' for water-
flow nonsilenceable.
Note that '0' is not a valid entry.
Input Channel 3 Function Selection (67)
Factory default for Channel 3 is '0' for activation on fire alarm (2-wire smoke). Enter '1' for pull station; '2' for
normally open contact device; '3' for host panel trouble; '4' for fire supervisory; '5' for fire supervisory autoresetta-
ble; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
Input Channel 4 Function Selection (68)
Factory default for Channel 4 is '1' for pull station. Enter '2' for normally open contact device; '3' for host panel
trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for waterflow silenceable; '7' for water-
flow nonsilenceable.
Note that '0' is not a valid entry.
Input Channel 1 Delay Timer (69 - 71)
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 1 Delay Timer is factory set to '000' seconds for no delay. The timer may be pro-
grammed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, the delay timer will also delay activation of
the relay, piezo sounder and LEDs.
Input Channel 2 Delay Timer (72 - 74)
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 2 Delay Timer is factory set to '000' seconds for no delay. The timer may be pro-
grammed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, the delay timer will also delay activation of
the relay, piezo sounder and LEDs.
Input Channel 3 Delay Timer (75 - 77)
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 3 Delay Timer is factory set to '000' seconds for no delay. The timer may be pro-
grammed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, the delay timer will also delay activation of
the relay, piezo sounder and LEDs.
1. Changing the input function will automatically change the corresponding Primary and Secondary event codes to reflect the new
input function. The Communication Format should be programmed first, followed by the Input Channel Function. See
"Events and Default Event Codes" on page 80.
2. This timer does not delay LED or Output Relay activation and is not used for channels programmed as AC Loss circuits.