4+2 Standard And 4+2 Express Formats - Primary - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Program Mode
4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes
If '1, A or C' is entered for address 20, the following data is automatically programmed for the Primary Central
Station phone number event codes. Enter '00' for the Setting to disable the report to the Central Station.

4+2 Standard and 4+2 Express Formats - Primary

TABLE 3-2:
Address
145 - 146
147 - 148
149 - 150
151 - 152
153 - 154
155 - 156
157 - 158
159 - 160
161 - 162
163 - 164
165 - 166
167 - 168
169 - 170
171 - 172
173 - 174
175 - 176
177 - 178
179 - 180
181 - 182
183 - 184
185 - 186
187 - 188
189 - 190
191 - 192
193 - 194
195 - 196
197 - 198
199 - 200
201 - 202
203 - 204
205 - 206
207 - 208
209 - 210
211 - 212
213 - 214
215 - 216
217 - 218
219 - 220
221 - 222
223 - 224
225 - 226
227 - 228
229 - 230
231 - 232
40
Description
Primary # Input Channel 1 Active Event Code
Primary # Input Channel 2 Active Event Code
Primary # Input Channel 3 Active Event Code
Primary # Input Channel 4 Active Event Code
Primary # Input Channel 1 Fault Event Code
Primary # Input Channel 2 Fault Event Code
Primary # Input Channel 3 Fault Event Code
Primary # Input Channel 4 Fault Event Code
Primary # AC Fault Event Code
Primary # Earth Fault Event Code
Primary # Low Battery Fault Event Code
Primary # No Battery Fault Event Code
Primary # Phone Line 1 Voltage Fault Event Code
Primary # Phone Line 2 Voltage Fault Event Code
Primary # NAC Fault Event Code
Primary # Charger Fault Event Code
Primary # Phone Number 1 Communication Fault Event Code
Primary # Phone Number 2 Communication Fault Event Code
Primary # System Off Normal Fault Event Code
Primary # Input Channel 1 Active Restore Code
Primary # Input Channel 2 Active Restore Code
Primary # Input Channel 3 Active Restore Code
Primary # Input Channel 4 Active Restore Code
Primary # Input Channel 1 Fault Restore Code
Primary # Input Channel 2 Fault Restore Code
Primary # Input Channel 3 Fault Restore Code
Primary # Input Channel 4 Fault Restore Code
Primary # AC Voltage Fault Restore Code
Primary # Earth Fault Restore Code
Primary # Low Battery Fault Restore Code
Primary # No Battery Fault Restore Code
Primary # Phone Line 1 Voltage Fault Restore Code
Primary # Phone Line 2 Voltage Fault Restore Code
Primary # NAC Fault Restore Code
Primary # Charger Fault Restore Code
Primary # Phone Number 1 Communication Fault Restore Code
Primary # Phone Number 2 Communication Fault Restore Code
Primary # System Off Normal Restore Code
Primary # System Test Message
Primary # System Abnormal Test Message
Primary # Upload/Download Request Code
Primary # Upload Successful Code
Primary # Download Successful Code
Primary # Upload/Download Failed Code
411UDAC
Document #51073
Rev. D 12/09/2008
Setting
11
12
13
14
F1
F2
F3
F4
92
61
62
63
64
65
66
47
6A
6B
6F
E1
E2
E3
E4
D1
D2
D3
D4
93
A1
A2
A3
A4
A5
A6
57
AA
AB
AF
99
91
71
72
73
74
P/N 51073:D