Program Mode
Secondary Central Station Number Communication Format (50)
One location is needed to select the Communication Format to the secondary phone number. Address 50 is used
for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
The Format selected in address 50 will cause the 411UDAC to automatically program addresses 229 - 312 with the
factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior to alter-
ing the event code settings. An entry of all zeros for any event code will cause the communicator to NOT transmit the
report. Transmission of reports to either or both Central Station phone numbers may be disabled.
Refer to "Central Station Communications" on page 55 for information on Format reporting.
Upon accessing the first event code address which is 229 (Refer to Table 3-5, "4+2 Standard and 4+2 Express For-
mats - Secondary," on page 45), the following may be displayed on the Programmer's 7-Segment Display, if the cor-
responding Format was selected in address 50.
The first three locations on the left of the Programmer's display represent the memory address 229. The last location
1 (farthest right) represents the contents of memory address 229 which is the first digit of the event code.
The following Tables list the data which is automatically programmed for each Format that can be selected in address
50. The addresses shown in each Table contain the event code Setting data which is automatically programmed by
the 411UDAC. To change the value, key in the new digits and then press the [ENTER/STORE] key to save the new
value. Use the Up and Down Arrow keys to increment to the next address or decrement to the previous address.
2291
(address) (data)
411UDAC
Document #51073
Rev. D 12/09/2008
P/N 51073:D
43