Program Mode
Input Channel 4 Delay Timer (78 - 80)
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 4 Delay Timer is factory set to '000' seconds for no delay. The timer may be pro-
grammed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, the delay timer will also delay activation of
the relay, piezo sounder and LEDs.
Touchtone/Rotary Select for Primary Phone (81)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the primary phone line. Select '1'
for rotary dialing.
Make/Break Ratio for Primary Phone (82)
This address is used only if a '1' has been programmed for address 81. The Make/Break ratio is factory set to '0'
which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (83)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the secondary phone line. Select
'1' for rotary dialing.
Make/Break Ratio for Secondary Phone (84)
This address is used only if a '1' has been programmed for address 83. The Make/Break ratio is factory set to '0'
which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
Output Relay #1 Enable (85)
The factory default setting for Output Relay #1 is '0' for disabled. Enter '1' to enable the relay.
Output Relay #1 Function Selections (86)
The Output Relay can be programmed to activate for any one of six conditions. The factory default for address 86
is '0' for activation on fire alarm. Program a '1' for host panel trouble; '2' for DACT trouble; '3' for latching fire
supervisory; '4' for autoresettable fire supervisory; '8' for total communication failure.
Output Relay #2 Enable (87)
The factory default setting for Output Relay #2 is '0' for disabled. Enter '1' to enable the relay.
Output Relay #2 Function Selections (88)
Output Relay #2 can be programmed to activate for any one of six conditions. The factory default for address 88
is '2' for activation on DACT trouble. Program a '0' for activation on fire alarm; '1' for host panel trouble; '3' for
latching fire supervisory; '4' for autoresettable fire supervisory; '8' for total communication failure.
Reserved for Future Use (89)
Leave default setting of '0'
Reserved for Future Use (90)
Leave default setting of '0'
1. This timer does not delay LED or Output Relay activation and is not used for channels programmed as AC Loss circuits.
1
411UDAC
Document #51073
Rev. D 12/09/2008
P/N 51073:D
49