Program Mode - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Program Mode

Enter the second minute digit (0 in this example) and press the [ENTER/STORE] key. The number '0' will appear as
the digit fourth from the left. Following the entry of the fourth and final digit, the operating mode will immediately
switch to Normal Mode, indicating that programming of the time is now completed.
To exit Real Time Clock Mode before completing clock programming, press the MODE key, followed by the 4-digit
code for an alternate mode and then the [ENTER/STORE] key. During Real Time Clock Mode, if no key is pressed
within 10 minutes, the 411UDAC will revert to Normal Mode.
Note that upon power-up, the internal clock starts running at 00:01 midnight. It must be changed so that the
411UDAC can accurately call in test signals to the Central Station. Upon power loss or on entering Default Mode,
the clock reverts to 00:01 midnight and must be reset.
3.3
Program Mode
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must
be limited to specific values or not used at all as indicated below:
Program feature
Permitted in
or option
UL 864? (Y/N)
Trouble Call Limit
All programming selections made during Program Mode are stored in nonvolatile Electrically-Erasable Programma-
ble Read-only Memory (EEPROM). This ensures that the 411UDAC will retain all entries made in Programming
Mode even if power is removed.
The user must program the primary and secondary phone numbers, account numbers, 24-hour test report times and
verify event codes for each Central Station account. The 411UDAC is shipped with the program options/features
already factory programmed. Alternative options/features may be programmed if desired. If all factory default set-
tings are acceptable, programming is complete.
Program Mode is entered by pressing the MODE key followed by the 4-digit program mode entry code 7764 and
pressing the [ENTER/STORE] key.
7764 spells PROG on a Touch-Tone
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as
information is entered into the 411UDAC, the digits will scroll across the Programmer display from right to left.
___7
__77
_776
7764
A pause of up to 10 seconds between each number is allowed while entering the code. After pressing the [ENTER/
STORE] key, the 411UDAC will be in Program Mode. A maximum of 10 minutes idle time is allowed at this point
before beginning program entries and between each key stroke, otherwise, the unit will return to Normal Mode. All
entries made prior to the 10 minute time-out are valid and are stored.
AND OTHER INVOLVED PARTIES
Program Address 96 = 0 (factory default): unlimited
calling to Central Station for any trouble condition
N
Program Address 96 = 1: limits call for each unique
trouble to 10 within a 24 hour period
®
phone.
411UDAC
Document #51073
Possible settings
Rev. D 12/09/2008
P/N 51073:D
Settings permitted
in UL 864
Program Address 96
= 0 for unlimited
Central Station
trouble calls
35