Format Selection Addresses ( 20 And 50) Programming - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Central Station Communications
The digital communicator is capable of reporting detailed messages depending upon the Format in use. Table 4-1
shows the data reporting structure for each of the pulsed formats as well as the Ademco Express Formats. Ademco
Express Formats allow a typical data message to be transmitted to the Central Station in under 5 seconds. Pulsed for-
mats typically require 15 to 20 seconds in comparison. Table 4-2 defines each letter code used in Table 4-1 . See
"Ademco Contact ID Format Event Code Description" on page 59 for a description of the data reporting structure for
Ademco Contact ID Format.

Format Selection Addresses ( 20 and 50) Programming

TABLE 4-1:
Report
Fire Alarm
Fire Alarm Restore
Channel/Input Trouble
(Channel/Input Open)
Channel/Input Trouble
Restore
System Trouble
System Trouble Restore
AC Loss
AC Loss Restore
Fire Supervisory Condition
Fire Supervisory Condition
Restore
Test Report
Up or Download
56
Format #
Format #
0, 2, 4, 6, 8
3, 5, 7, 9
3+1/4+1/Standard
3+1/4+1/Expanded
4+1 Express
SSS(S) FA
SSS(S) FA
FAFAFA(FA) 2
SSS(S) RFA
SSS(S) RFA
RFARFARFA (RFA) 2
SSS(S) TZ
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSS(S) TS
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSS(S) P
SSS(S) P
PPP(P) Z
SSS(S) RP
SSS(S) RP
RPRPRP(RP) Z
SSS(S) V
SSS(S) V
VVV(V) Z
SSS(S) RV
SSS(S) RV
RVRVR(RV) Z
SSS(S) X
SSS(S) X
SSS(S) UD
SSS(S) UD
411UDAC
Document #51073
Format #
1, A, C
4+2/Standard 4+2
4+2/Expanded
Express
SSSS FAFA2
SSSS RFARFA2
SSSS TZTZ2
SSSS RTZRTZ2
SSSS TSTS2
SSSS RTSRTS2
SSSS PP2
SSSS RPRP2
SSSS RPRP2
SSSS VV2
SSSS RVRV2
SSSS XX2
SSS UDUD2
SSS UDUD2
Rev. D 12/09/2008
P/N 51073:D
Format #
B, D
SSSS FAZ
SSSS RFAZ
SSSS TZZ
SSSS RTZZ
SSSS TSY
SSSS RTSY
SSSS PP2
SSSS VZ
SSSS RVZ
SSSS XX2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Firewatch 411udac

Table of Contents