Omron VARISPEED F7 Quick Manual page 21

200v class 3-phase 0.4 to 110 kw 400v class 3-phase 0.4 to 300 kw
Hide thumbs Also See for VARISPEED F7:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Param-
eter
Name
Num-
ber
Torque Limit (only OLV and CLV)
Forward drive
L7-01
torque limit
Reverse drive
L7-02
torque limit
Forward
L7-03
regenerative
torque limit
Reverse
L7-04
regenerativ
torque limit
Monitor Data
U1-01 Frequency reference in Hz / rpm
U1-02 Output frequency in Hz / rpm
U1-03 Output current in A
U1-06 Output voltage in VAC
U1-07 DC bus voltage in VDC
U1-08 Output power in kW
U1-09 Torque reference
Input terminal
U1-10
status
Output termi-
U1-11
nal status
Operation
U1-12
status
U1-13 Cumulative operation time in hrs.
U1-21 ASR input
U1-22 ASR output
U1-34 OPE fault parameter
U1-40 Cooling fan operating time in hrs.
EN-20
Description
Sets the torque limit vlaue as a per-
centage of the motor rated torque.
Four individual regions can be set.
Output torque
Positive torque
No.
motor
Regen.
Reverse
rotations
Forward
Regen.
Negative torque
Shows input ON/OFF status.
U1-10 =
1: FWD command
(S1) is ON
1: REV command
(S2) is ON
1: Multi input 1
(S3) is ON
1: Multi input 2
(S4) is ON
1: Multi input 3
(S5) is ON
1: Multi input 4
(S6) is ON
1: Multi input 5
(S7) is O N
Shows output ON/OFF status.
U1-11 =
1: Multi-function
contact output 1
(M1-M2) is ON
1: Multi-function
contact output 2
(M3-M4) is ON
1: Multi-function
contact output 3
(M5-M6) is ON
Not used
(Always 0).
1: Error output
(MA/MB-MC) is ON
Inverter operating status.
U1-12 =
Run
1: Zero speed
1: Reverse
1: Reset signal input
1: Speed agree
1: Inverter ready
1: Minor fault
1: Major fault
Param-
eter
Name
Num-
ber
Fault Trace Data
U2-01 Current fault
U2-02 Last fault
U2-03 Reference frequency at fault
U2-04 Output frequency at fault
U2-05 Output current at fault
o
U2-07 Output voltage reference at fault
U2-08 DC bus voltage at fault
U2-09 Output power at fault
U2-11 Input terminal status at fault
U2-12 Output terminal status at fault
U2-13 Operation status at fault
U2-14 Cumulative operation time at fault
Fault History Data
U3-01
to
Last fault to fourth last fault
U3-04
U3-05
to
Cumulative operation time at fault 1 to 4
U3-08
U3-09
to
Fifth last to tenth last fault
U3-14
U3-15
to
Accumulated time of fifth to tenth fault
U3-20
* The following faults are not recorded in the error log:
CPF00, 01, 02, 03, UV1, and UV2.
Digital Input Function Selections (H1-01 to H1-05)
3
Multi-step speed reference 1
4
Multi-step speed reference 2
5
Mulit-step speed reference 3
Jog frequency command (higher priority than multi-
6
step speed reference)
7
Accel/decel time selection 1
F
Not used (Set when a terminal is not used)
14
Fault reset (Reset when turned ON)
19
PI control disable
External fault; Input mode: NO contact/NC contact,
20 to
2F
Detection mode: Normal/during operation
71
Speed/torque control change (ON: Torque control)
77
Speed control (ASR) gain switching (ON: C5-03)
Digital Output Function Selections
(H2-01 and H2-02
During run 1 (ON: run command is ON or voltage is
0
being output)
Inverter operation ready; READY: After initialization or
6
no faults
F
Not used. (Set when the terminal is not used.)
10
Minor fault (Alarm) (ON: Alarm displayed)
1A
During reverse run (ON: During reverse run)
Motor overload (OL1, including OH3) pre-alarm (ON:
1F
90% or more of the detection level)
During torque limit (current limit) (ON: During torque
30
limit)
Activated if the ASR is operating for torque limit. The
32
ASR output becomes the torque reference, the motor
is rotating at the speed limit.
Description