• For external control power supply use a UL Listed Class 2 power supply.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating
faults.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields should be grounded on both cable ends.

Main Circuit Terminals

Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
B1, B2
+1, +2
+1, –
(2 terminals)
Main Circuit Terminals
The figure below shows the control circuit terminal arrangement. The drive is equipped with
screwless terminals
There are three DIP switches, S1 to S3, located on the terminal board
SW1
Switches analog input A2 between voltage and current input
SW2
Enables or disables the internal RS422/485 comm. port terminal resistance.
Used to select sourcing (PNP)/sinking (NPN, default) mode for the digital inputs (PNP requires
SW3
external 24 Vdc power supply)
I67E-EN
V1000 Quick Start Guide
Type
Connects line power to the drive.
Main circuit power
Drives with single-phase 200 V input power use terminals R/L1 and S/
supply input
L2 only (T/L3 is not used).
Drive output
Connects to the motor.
Braking resistor
For connecting a braking resistor or the braking resistor unit option.
DC reactor connec-
Linked at shipment. Remove the link to install a DC choke.
tion
DC power supply
For connecting a DC power supply.
input
For 200 V class: Ground with 100 Ω or less
Ground Terminal
For 400 V class: Ground with 10 Ω or less
R+ R- S+ S- IG
P1 P2 PC A1 A2 +V AC AM AC MP
S1 S2 S3 S4 S5 S6 SC HC H1 H2 RP
S2
S1
S3
MA MB MC
3 Electrical Installation