6 Parameter Table
Par.
Name
Digital Input Settings
DI S1 to
H1-01
S6
Selects the function of terminals S1
to
Function
to S6.
H1-06
Selection
A list of the major functions can be found at the table end.
Digital Output Settings
DO
Set the function for the relay output
H2-01
MA/MB
MA-MB-MC.
Function
DO P1
Sets the function for the photocou-
H2-02
Function
pler output P1.
DO P2
Sets the function for the photocou-
H2-03
Function
pler output P2.
Major functions are listed at the end of the table.
Analog Input Setting
A1 Signal
0:0 to +10 V (neg. input is zeroed)
H3-01
Level Sel.
1:0 to +10 V (bipolar input)
A1
Func-
H3-02
Assign a function to terminal A1.
tion Sel.
Sets the input value in % at 10 V
H3-03 A1 Gain
analog input.
Sets the input value in % at 0 V
H3-04 A1 Bias
analog input.
0:0 to +10 V (neg. input is zeroed)
A2 Signal
1:0 to +10 V (bipolar input)
H3-09
Level
2:4 to 20 mA (9 bit input)
Selection
3:0 to 20 mA
A2
Func-
H3-10
Assign a function to terminal A2.
tion Sel.
Sets the input value in % at
H3-11 A2 Gain
10 V /20 mA analog input.
Sets the input value in % at
H3-12 A2 Bias
0 V / 0 mA / 4 mA analog input.
Analog Input Setting
AM
Enter value equal to U1-
H4-01
Monitor
monitor values. Example: Enter
Selection
"103" for U1-03.
Sets terminal AM output voltage
H4-02 AM Gain
equal to 100% monitor value.
Sets terminal AM output voltage
H4-02 AM Bias
equal to 0% monitor value.
24
Description
Par.
Name
Pulse Input Setting (Free. ref. input)
RP Input
Sets the number of pulses (in Hz)
H6-02
Scaling
that is equal to 100% input value.
Pulse Train
Sets the input value in % at pulse
H6-03
Input Gain
input with H6-02 frequency.
Pulse Train
Sets the input value in % at 0 Hz
H6-04
Input Bias
pulse input frequency.
Pulse Output Setting
MP
Enter value equal to U -
H6-06
Monitor
monitor values. Example: Enter
Sel.
"102" for U1-02.
MP Monitor
Sets the number of output pulses
H6-07
Scaling
when the monitor is 100% (in Hz).
Motor Overheat Protection
Sets the motor overload protection.
Motor
0:Disabled
L1-01
Overload
1:Standard fan cooled motor
Prot. Sel.
2:Standard blower cooled motor
3:Vector motor
Motor
Sets the motor overload protection
L1-02
Overload
time in min. Normally no change is
Prot. Time
necessary.
Stall Prevention
0:Disabled - Motor accelerates at
active acceleration rate and may
Stall
stall with too heavy load or too
Prevention
short accel time.
Selection
L3-01
1:General
during
acceleration when current is
Accelera-
above L3-02.
tion
2:Intelligent - Acceleration in the
shortest possible time.
Stall
Prev.
Sets the current level for stall pre-
L3-02
Level
dur-
vention during acceleration.
ing Accel.
0:Disabled - Deceleration as set.
Stall
Prev.
OV might occur.
Selection
L3-04
1:General Purpose - Deceleration
during
is hold if DC bus voltage rises
Decel.
high.
0:Disabled
Stall
Prev.
overload might occur.
L3-05
Selection
1:Decel Time 1 - Reduce speed
during Run
using C1-02.
I67E-EN
Description
Purpose
-
Hold
-
Motor
stall
or
V1000 Quick Start Guide