Omron V1000 Quick Start Manual page 24

Compact current vector inverter
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Par.
Name
C1-03
Accel/Decel
Set the accel/ decel times 2 to 4 (set
to
Times 2 to 4
like C1-01/02)
C1-08
C2-01 S-Curve 1
S-curve at acceleration start.
C2-02 S-Curve 2
S-curve at acceleration end.
C2-03 S-Curve 3
S-curve at deceleration start.
C2-04 S-Curve 4
S-curve at deceleration end.
Slip Compensation
• Increase if the speed is lower than
Slip
Com-
the frequency reference
C3-01
pensation
• Decrease if the speed is higher
Gain
than the frequency reference.
• Decrease the setting when the slip
Slip
Com-
compensation is too slow.
C3-02
pensation
• Increase the setting when the
Delay Time
speed is not stable.
Torque Compensation
• Increase this setting when the
Torque
torque response is slow
C4-01
Compensa-
• Decrease this setting when speed/
tion Gain
torque oscillations occur.
Torque
• Increase this setting when speed /
Compensa-
torque oscillations occur.
C4-02
tion
Delay
• Decrease the setting when the
Time
torque response is too slow.
Duty Mode and Carrier Frequency
0: Heavy Duty (HD)
Normal/
Constant torque applications
C6-01
Heavy Duty
1:Normal Duty (ND)
Selection
Variable torque application
1:2.0 kHz
2:5.0 kHz
3:8.0 kHz
Carrier Fre-
4:10.0 kHz
C6-02
quency
5:12.5 kHz
Selection
6:15.0 kHz
7 to A: Swing PWM1 to 4
F: User defined
Frequency References
d1-01
Frequency
Set the multi-speed references 1 to
to
Reference
16
d1-16
1 to 16
d1-17 Jog Speed
Jog speed
I67E-EN
V1000 Quick Start Guide
Description
Par.
Name
V/f Pattern
Input
E1-01
Voltage Set-
Input Voltage
ting
Max.
Out-
For a linear V/f characteristics, set
E1-04
put Freq.
the same values for E1-07 and E1-
09. In this case, the setting for E1-
Max.
Out-
E1-05
08 will be disregarded.
put Voltage
Ensure that the four frequencies are
set according to these rules or
Base
Fre-
E1-06
OPE10 fault will occur:
quency
Middle Out-
E1-04 ≥ E1-06 ≥ E1-07 ≥ E1-09
E1-07
put Freq.
Output voltage
Mid.
Out-
(E1-05)
E1-08
(E1-13)
put Voltage
Min.
Out-
E1-09
put Freq.
(E1-08)
Min.
Out-
E1-10
put Voltage
(E1-10)
Base
E1-13
Voltage
Motor Data
Motor
Automatically
E2-01
Rated
Auto-Tuning.
Current
Motor rated slip in hertz (Hz).
Motor
E2-02
Automatically set by Rotational
Rated Slip
Auto-Tuning.
Motor
Magnetizing current in Ampere.
E2-03
No-Load
Automatically set by Rotational
Current
Auto-Tuning.
Number of motor poles.
E2-04 Motor Poles
Automatically set by Auto-Tuning.
Motor Line-
Sets the phase-to-phase motor
E2-05
to-Line
resistance in ohms.
Resistance
Automatically set by Auto-Tuning.
Sets the voltage drop due to motor
Motor
leakage inductance as a percentage
E2-06
Leakage
of motor rated voltage.
Inductance
Automatically set by Auto-Tuning.
6 Parameter Table
Description
(E1-09)
(E1-07)
(E1-06)
Output frequency
set
(E1-04)
during
23