Installation notes
3-1
Installation notes
3-1-1
Location
3-1-2
Temperature control
3-1-3
Accessibility
3-1-4
Panel cut-out
8
For improved reliability and maximized functionality, take the following
information into consideration when installing a NQ-Series HMI.
Do not install the NQ-Series in the following locations:
•
Areas subject to explosion hazards due to flammable gasses, vapours and
dusts.
•
Areas subject to dramatic temperature changes. Temperature changes can
cause condensation of water in the device.
•
Areas with an ambient temperature lower than 0 °C or higher than 50 °C.
•
Areas subject to shock or vibration.
•
Provide adequate space for air flow.
•
Do not install the NQ-Series above equipment that generates significant
heat.
•
If the ambient temperature exceeds 50 °C, install a cooling fan or air
conditioner.
•
For safety during operation and maintenance, mount the NQ-Series as far
as possible from high-voltage equipment and power machinery.
Before the NQ-Series can be mounted, a rectangular cut-out must be made in
the panel in which the NQ-Series will be mounted. Table 3.1: Dimensions of
NQ-Series and required panel cut-out shows the dimensions and tolerances of
the NQ-Series, the panel and the required cut-out.
/i
Table 3.1: Dimensions of NQ-Series and required panel cut-out
Display size
External dimensions:
Panel cut-out:
Panel cut-out tolerance
Panel thickness
Above external dimensions and cut-outs are for landscape models.
For portrait models exchange the W and H sizes. For portrait models the
cables will be mounted to the left side of the NQ-Series (view from front).
NQ5-
5.7 "
W
195 mm
ext
H
142 mm
ext
W
184.00 mm
cut-out
H
131.00 mm
cut-out
+0.50 mm
Max. 6.0 mm
Section 3-1
NQ3-
3.5 " and 3.8 "
128 mm
102 mm
119.00 mm
93.00 mm
+0.50 mm
Max. 6.0 mm