CompoNet Explicit Messages
Explicit Messages for Digital I/O Slave Units
Setting and Monitoring Inputs
Explicit
Read/
message
write
Terminal
Read
Reads the monitor
Mainte-
mode for maintenance
nance Infor-
information of the input
mation
(No. 1 to 32) specified
Monitor
by the Instance ID.
Mode
Write
Writes the monitor
mode for maintenance
information of the input
(No. 1 to 32) specified
by the Instance ID.
Set Value
Read
Reads the set value for
for Input
the total ON time (unit:
Total ON
s) or number of contact
Time or
operations (unit: opera-
Contact
tions) of the input (No.
Operation
1 to 32) specified by
Counter
the Instance ID.
Write
Writes the set value for
the total ON time (unit:
s) or number of contact
operations (unit: opera-
tions) of the input (No.
1 to 32) specified by
the Instance ID.
Input Total
Read
Reads the total ON
ON Time or
time (unit: s) or number
Contact
of contact operations
Operation
(unit: operations) for
Counter
the input (No. 1 to 32)
Read
specified by the
Instance ID.
Input Total
Reset
Resets the total ON
ON Time or
time (unit: s) or number
Contact
of contact operations
Operation
(unit: operations) for
Counter
the input (No. 1 to 32)
Reset
specified by the
Instance ID.
Monitor
Read
Reads the monitor sta-
Status for
tus for total ON time or
Input Total
number of contact
ON Time or
operations for the input
Contact
(No. 1 to 32) specified
Operation
by the Instance ID.
Counter
Read
Function
Service
code
0E hex
10 hex
0E hex
10 hex
0E hex
05 hex
0E hex
Command
Class
Instance
Command data
ID
ID
Attribute
ID
08 hex 01 to 20
65 hex
hex
08 hex 01 to 20
65 hex
hex
08 hex 01 to 20
68 hex
hex
08 hex 01 to 20
68 hex
hex
08 hex 01 to 20
66 hex
hex
08 hex 01 to 20
66 hex
hex
08 hex 01 to 20
67 hex
hex
Appendix A
Response
Service data
Data
---
1 byte
00 hex: Total ON
time mode
01 hex: Contact
operation
counter mode
1 byte
---
00 hex: Total
ON time
mode
01 hex: Con-
tact opera-
tion counter
mode
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
4 bytes
---
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
---
---
---
1 byte
00 hex: Within
range
01 hex: Out of
range (over the
monitor value)
595