Units with Screw Terminal Blocks
5-3-6
Eight-point Output Units (2-tier Terminal Block with Relay
Outputs)
CRT1-ROS08
Common Specifications
Communications power supply voltage
Noise immunity
Vibration resistance
Shock resistance
Dielectric strength
Insulation resistance
Ambient operating temperature
Ambient operating humidity
Ambient operating atmosphere
Storage temperature
Storage humidity
Terminal block screws tightening torque
Relay Output Section Specifications (per Output)
Item
Item
Model
I/O capacity
Mounted Relays
Rated load
Rated ON current
Maximum contact voltage
Maximum contact current
Maximum switching capacity
Minimum applicable load (reference
value)
Mechanical service life
Electrical service life
Installation method
Communications power supply current
consumption
Output hold for communications errors
Weight
Note
(1) With a current of between 2 and 3 A (8 to 10 A per common), either en-
sure that the number of points per common that simultaneously turn ON
does not exceed 4 or ensure that the temperature does not exceed 45°C.
There are no restrictions if the current does not exceed 2 A (8 A per com-
mon).
(2) The rated current is the value for assuring normal operation, and not for
assuring durability of the relays. The relay service life depends greatly on
factors such as the operating temperature, the type of load, and switching
Specification
14 to 26.4 VDC
Conforms to IEC 61000-4-4, 2 kV (power line).
10 to 55 Hz with double-amplitude of 0.7 mm
2
100 m/s
(3 times in 6 directions on 3 axes)
500 VAC (between isolated circuits)
20 MΩ min. (between isolated circuits)
−10 to 55°C
25% to 85% (with no condensation)
No corrosive gases
−25 to 65°C
25% to 85% (with no condensation)
M3 wiring screws: 0.5 N⋅m
M3 mounting screws: 0.5 N⋅m
Specification
CRT1-ROS08
8 outputs
DRTA-NY5W-K (5 VDC)
Resistive load
250 VAC, 2 A, common: 8 A
30 VDC, 2 A, common: 8 A
3 A
250 VAC, 125 VDC
3 A
750 VA AC, 90 W DC
5 VDC, 1 mA
20,000,000 operations min.
100,000 operations min.
DIN Track
95 mA max. for 24-VDC power supply voltage
150 mA max. for 14-VDC power supply voltage
Select either hold or clear from CX-Integrator.
170 g max.
Section 5-3
147