Connecting to Screw-less Clamp Terminal Blocks

Note
When using a DCN4-MD4 Multidrop Connector to branch a Communications
Cable, bind together the loose wires where the cable comes out of the Hood
Cover. Wire the Communications Cable and loose-wire cable so that they do
not interfere with each other.
For Slave Units with screw-less clamp terminal blocks, the terminal blocks can
be easily wired by inserting pin terminals. Follow the procedure below to con-
nect the external device cable to a screw-less clamp terminal block.
■ Applicable Pin Terminals
When wiring an external device cable to a screw-less clamp terminal block,
special pin terminals must be placed on the cable wires. The applicable pin
terminals are listed in the following table.
Name
H0.5/14 orange
H0.75/14 white
H1.5/14 red
The pin terminal conductor should be about 8 to 10 mm in length.
Conductor length: 8 to 10 mm
■ Wiring to the Screw-less Clamp Terminal Block
Inserting Pin Terminals
Insert the pin terminal all the way to the back of the terminal hole.
Insert the pin terminal all the way to the back.
Removing Pin Terminals
Press down the release button next to the terminal hole with a small flat-blade
screwdriver and pull out the pin terminal while the release button is down.
Small flat-blade screwdriver
Release button
The following screwdriver is recommended for removing pin terminals.
Model
SD0.6 × 3.5 × 100 Flat-blade
Screwdriver
Applicable wire size
Crimp tool
2
0.5 mm
/AWG20
PZ6 roto
2
0.75 mm
/AWG18
2
1.5 mm
/AWG16
Manufacturer
Weidmuller Co. Ltd.
Section 3-6
Manufacturer
Weidmuller Co. Ltd.
111