Two-Point Analog Output Slave Unit (With Mil Connectors) - Omron CRT1 - 10-2009 Operation Manual

Componet slave units and repeater unit
Table of Contents

Advertisement

Units with Connectors
6-7-4

Two-point Analog Output Slave Unit (with MIL Connectors)

CRT1-VDA02ML
General Specifications
Item
Model
Output signal ranges
External output allowable load resistance
Resolution
Overall accuracy
25°C
–10 to 55°C
Conversion cycle
DA conversion data
Isolation method
Mounting
Power supply type
Communications power current consumption
Weight
Note
356
■ When a DCN4-MD4 Multidrop Connector Is Mounted
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
1 kΩ min.
1/6,000 (full scale)
±
0.4% FS
±
0.8% FS
2 ms/ 2 points
–10 to 10 V range: F448 to 0BB8 hex full scale (–3,000 to 3,000)
Other ranges: 0000 to 1770 hex full scale (0 to 6,000)
DA conversion range:
Photocoupler isolation (between output and communications lines)
No isolation between output signal wires.
DIN Track mount or mount for Mounting Bracket
Multi-power supply
105 mA max. for 24-VDC power supply
170 mA max. for 14-VDC power supply
75 g max.
The specified accuracy does not apply below 0.2 mA when using the 0 to
20 mA range.
(mm)
Specification
Voltage Output
CRT1-VDA02ML
0 to 20 mA
4 to 20 mA
600 Ω max.
±
±
±
5% FS of the above data ranges.
Section 6-7
Current Output
0.4% FS (See note.)
0.8% FS (See note.)