Mitsubishi Electric e Series Service Handbook page 50

Hide thumbs Also See for e Series:
Table of Contents

Advertisement

[ II Restrictions ]
[3] Inside header piping type
Installing the straub joint
HWE20010
150A housing type joint
N
L
W
d
G
Groove detail
C0.5
C0.5
R
The seal rubber has a lip
construction to improve water
stopping performance.
Adjust the Straub position to that
the marking on both sides is visible.
The bolts need only be tightened until
the casing is sealed (metal touches).
Consequently, the procedure can be
carried out accurately by anyone to the
same level, regardless of worker
proficiency or the type of pipe.
Water outlet
Connection detail
Groove pipes at chiller side
d
G
W
L
N
R
- 41 -
Water inlet
Straub joint
The dimension of the groove pipe
at the chiller side
(Unit: mm)
Pipe size
6B (150A)
ø165.1
ø160.8
+ 0.7
8.7
– 0
+ 0.7
15.9
– 0
50.0
1.0
Marking
W
θ θ
θ
Allowable tolerance for gaps and tilting
Pipe gap tolerance [W]: 0 to 25 mm
Allowable pipe tilt angle [ ]: ±2°
GB