[ II Restrictions ]

[4] Configuring the Settings

The settings must be set only by a qualified personnel.
1. System configuration
(1) Set the dip switches. (System setting)
Switch settings on the MAIN circuit
Set the dip switches (labeled A in the figure at
right) that correspond to the items below,
according to the local system.
• Water temperature control based on the
external water temperature reading
• Analog signals from a remote location
Refer to "Table of settings items" for further
details. (Page 32-33)
(2) M-NET address setting
Example of address setting
Field-supplied dry
contact switch/relay,
remote controller or
centralized controller
External temperature
sensor 1 (option)
Flow switch
Pump interlock
External temperature
sensor 2 (option)
External temperature
sensor 1 (option)
Flow switch
Pump interlock
External temperature
sensor 1 (option)
Flow switch
Pump interlock
ON
1
2
3
4
5
6
7
8
9 10
HWE20010
MAIN circuit board
1
2
System leader
Sub unit
unit
SUB MAIN
SUB MAIN
51
1
52
M-NET line
7
8
Group leader
Sub unit
unit
SUB MAIN
SUB MAIN
57
7
58
19
20
Group leader
Sub unit
unit
SUB MAIN
SUB MAIN
69
19
70
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
A
6
Sub unit
SUB MAIN
2
56
6
12
Sub unit
SUB MAIN
8
62
12
24
Sub unit
SUB MAIN
20
74
24
- 28 -
SUB circuit board
Simultaneous
operating group
(Max 6 units)
Simultaneous
Identical water
operating group
system group
(Max 6 units)
(Max 24 units)
Simultaneous
operating group
(Max 6 units)
GB