[ II Restrictions ]
3. Setting procedures
(1) Example of system setting
1. Making the settings for the initial start-up process
(A) Single unit
Remote
controller
(B) One system leader unit and two sub units (1 group, 3 units in the group)
RA
Remote
controller
Setting address 1
) 1
Turn off the power.
2)
System leader unit (Address 1 SW5-2, 5-3: ON)
3)
Turn the power back on.
Address 1
Address 51
4)
Setting the number of units for the group
SW7: 1 ON
SW4: 1, 2, 3, 4, 8, 10 ON
Press ENTER once.
Address 1
Press UP twice.
Address 1
Press ENTER once.
SW4 OFF
*The default setting for the number of units in a group is 1.
The maximum number of units per group is 6.
HWE20010
Address [1/51]
System leader unit
RA
RB
M1
M2
Address [1/51]
System leader unit
RB
M1
M2
LED display [EEEE]
→ LED display [9999]
→ LED display [1]
→ LED display [3]
Setting address 1
1)
Turn off the power.
2)
System leader unit (Address 1 SW5-2, 5-3: ON)
3)
Turn the power back on.
Address 1
Address 51
4)
SW7: 1, 2, 3, 4 ON and ENTER for 5 seconds.
(Initializes the system)
Address 1
Address 51
5)
Start-up process complete
Address 1
Address 51
6)
SW7 OFF
*No settings are required for address 51.
Address [2/52]
Address [3/53]
Sub unit
Sub unit
M1
M2
M1
5)
SW7: 1, 2, 3, 4 ON and ENTER for 5 seconds.
(Initializes the system)
Address 1
Address 51
6)
Start-up process complete
Address 1
Address 51
7)
SW7 OFF
*No settings are required for any address other than for
address 1.
- 34 -
→ LED display [EEEE]
→ LED display [9999]
→ LED display [9999]
→ LED display [9999]
→ LED display [____||_|]
→ LED display [____||_|]
M2
→ LED display [9999]
→ LED display [9999]
→ LED display [____||_|]
→ LED display [____||_|]
GB