Long Wiring Application - Delta VP3000 Series User Manual

Open-loop variable-torque standard drive
Table of Contents

Advertisement

Chapter 3 Electrical Wiring|VP3000

3-8 Long Wiring Application

Motor Cable Length
Consequence of leakage current on the motor
1.
If the cable length is too long, the stray capacitance between cables increases and may cause
leakage current. In this case, It activates the over-current protection, increases leakage current, or
may affect the current display. The worst case is that it may damage the AC motor drive. If more
than one motor is connected to one AC motor drive, the total wiring length should be the sum of the
wiring length from AC motor drive to each motor. For the 460V series AC motor drive, when you
install an overload thermal relay between the drive and the motor to protect the motor from
overheating, the connecting cable must be shorter than 50 m; however, an overload thermal relay
malfunction may still occur. To prevent the malfunction, install an output reactor (optional) to the
drive or lower the carrier frequency setting.
Consequence of the surge voltage on the motor
2.
When a motor is driven by a PWM-type AC motor drive, the motor terminals experience surge
voltages (dv/dt) due to power transistor conversion of AC motor drive. When the motor cable is
exceptionally long (especially for the 460V series), surge voltages (dv/dt) may damage the motor
insulation and bearing. To prevent this, follow these rules:
Use a motor with enhanced insulation (refer to the table below).
a.
Reduce the cable length between the AC motor drive and motor to suggested values.
b.
Connect an output reactor (optional) to the output terminals of the AC motor drive.
c.
Refer to the following tables for the suggested motor shielded cable length. Use a motor with a rated
voltage ≤ 500 VAC and insulation level ≥ 1.35 kV in accordance with IEC 60034-17.
460V
Model
VFD3A0VP43A
VFD4A2VP43A
VFD5A6VP43A
VFD7A2VP43A
VFD011VP43A
VFD013VP43A
VFD018VP43A
VFD025VP43A
VFD032VP43A
VFD038VP43A
VFD045VP43A
VFD062VP43A
VFD073VP43A
VFD091VP43A
VFD110VP43A
Rated Current
(Arms)
kW
HP
Normal Duty
0.75
1
3
1.5
2
4.2
2.2
3
5.6
3
4
7.2
4
5.3
11
5.5
7.5
13
7.5
10
18
11
15
25
15
20
32
18.5
25
38
22
30
45
30
40
62
37
50
73
45
60
91
55
75
110
Without an AC output reactor
Shielded Cable
Non-shielded
(meter)
Cable (meter)
50
75
50
75
50
75
50
75
50
75
50
75
100
150
100
150
100
150
100
150
100
150
100
150
100
150
150
225
150
225
136
With an AC output reactor
Shielded Cable
Non-shielded
(meter)
Cable (meter)
75
115
75
115
75
115
75
115
75
115
75
115
150
225
150
225
150
225
150
225
150
225
150
225
150
225
225
325
225
325