Chiller Description; Chiller Scope; Chiller Capacities; System Description - Trane TACW Series Installation, Operation And Maintenance Manual

Packaged water-cooled magnetic bearing chiller
Table of Contents

Advertisement

Chiller Description

Chiller Scope

This manual provides relevant data to properly operate,
maintain, and troubleshoot the Trane Packaged TACW
chiller. Operator and maintenance personnel must be a
qualified refrigeration technician and have a working
knowledge of high voltage systems, low voltage control
circuits, and components and functions.

Chiller Capacities

The Packaged TACW chillers utilize flooded shell and tube
evaporators and condensers. They are available from 110
to 600 tons.
These chillers consist of an evaporator, condenser, twin-
turbine centrifugal compressor(s), compressor controller,
and interconnecting refrigerant piping. The chiller requires
connection to the condenser and chilled water circuits, as
well as the main electrical supply and control wiring.
The thermal capacity of these units is dependent on the
leaving temperature of the chilled fluid, maintaining a
minimum flow of fluid through the evaporator and keeping
debris out of the system. In applications where it is desired
to operate with a lower flow rate or higher temperature,
consult the factory for recommendations.
Water quality must be monitored and maintained by a
water treatment professional familiar with the materials of
construction and operation of the equipment. The
equipment arrives fully charged with refrigerant. As
required under Federal regulations, installation, initial start-
up, and technical servicing should only be performed by
fully qualified personnel.

System Description

All Packaged TACW chillers are designed with a very small
approach to enhance the compressor performance
resulting in an outstanding IPLV rating. Chillers are
available in different configurations and with various
standard options including different compressor models to
customize these chillers to your specific applications.

Standard Features

ETL and AHRI Certified
10 kA SCCR Rating
One to four Danfoss Turbocor Variable Speed,
Magnetic Bearing, Oil-Free Centrifugal Compressor(s)
Unprecedented Part-Load Performance, High Energy
Efficiency, and Quiet Operation
5 percent Line Reactor per Compressor
Mounted Fused Isolation Switch per Compressor
Standard Single Point Power Connection
Dual Manifold Pressure Relief Valve
8
Danfoss Turbocor MCX Controller Complete with 10
inch Schneider HMI (Colored Monitor)
Including a Web Server Allowing Remote Internet
Monitoring, Remote Control, and Access to Operational
Logs and Software Updates
BACnet/LonWorks/ModBus Included Standard
Shell and Tube and Evaporator and Condenser
ASME/CRN Certified Cleanable Flooded Shell and
Tube Condenser, with Standard 150 psi Design
Pressure
Standard Flow Switch Located at Evaporator and
Condenser Hydronic Inlets
An Electronic Expansion Valve per Circuit Providing
Precise PLC Controlled Refrigerant Flow
3/4 inch (19 mm) Closed-Cell Insulation
First year parts, refrigerant, and Labor Warranty
Chillers are leak and pressures tested at 200 psig at high
side, 150 psig at low side, then evacuated and charged.
Self-contained chillers are equipped with a single source
power source and integral hydronic piping.
Unit panels, structural elements and control enclosure are
constructed of heavy-gauge powder coated aluminum and
mounted on sand blasted welded structural steel base and
painted with two parts epoxy paint for weather protection.

Optional Features

Waterbox Condenser/Evaporator
300 PSI Waterbox Condenser/Evaporator
300 PSI Marine Waterbox Condenser/Evaporator
Waterbox Hinges Condenser/Evaporator
Epoxy Coated Condenser/Evaporator
Flanged Connection Condenser/Evaporator
Fused/Non-Fused Disconnect Switch
Low Lift Refrigeration Pump
Passive Harmonic Filters
Rapid Restart
Full/Partial Knockdown
Remote Monitoring Wireless Module
Compressor Wraps
Isolation Pads
1.5-inch Insulation
ARTC-SVX014A-EN