Operating Procedures
Table 22. Hot gas low balancing control
Screen
Hot Gas Bypass
Valves Control
Hot Gas Bypass
Valve Setup
Hot Gas Bypass
Valves Manual
Control
Low-Lift Application
The low-lift application uses a special expanded-map
compressor with a refrigerant motor cooling pump. With a
standard lift compressor, motor cooling is dependent on a
pressure of 1.5 or better to push liquid refrigerant into the
cooling ports of the compressors. In Low-Lift, the
refrigerant pump pushes the liquid refrigerant into the
cooling ports allowing for the chiller to drop the pressure
ratio to ~1. This low-pressure ratio leads to near free-
cooling efficiencies.
This function is enabled by mode selection.
1. Disabled – No operation.
2. Motor Cooling – Function provides cooling to
compressor motor only.
3. Split System – Function provides both motor cooling
and flow boost to EXV.
58
User Interface
Function
Displays trend and current values for Setpoint,
Process Value and Valve position.
PV. Chiller LWT.
SP. SP = Chiller SP – low urgency zone (refer
to Chiller Control Manual) + SP Offset
(described below).
T3C dP. Evaporator inlet / outlet pressure delta.
Trend has y-axis zoom capability.
Provides access to other pop-up screens:
Setup
HGVs
Solenoids
SP Offset. Involved in setpoint calculation (see
main screen SP description above)
P-Gain and I PID constants.
Each Hot Gas Bypass valve can be in one of the
following modes:
Auto. Valve controlled automatically by Hot
Gas Bypass PID controller (solenoid opens
when PID opens the modulating valve)
Off. Valve is always off;
Manual. Valve position is set up manually.
This section focuses on the motor cooling mode of the low-
lift application. In this mode, the controller looks at the
pressure ratio and uses a threshold setpoint to enable the
function as a permissive. The refrigerant pump is controlled
by the same threshold values that the compressor uses to
open its own motor cooling valves.
Inputs
Compressor pressure ratio
Inverter Temperature
Cavity Temperature
Compressor Run. – Compressor must be running to
use this function.
Parameters
Pressure Ratio Threshold – If the pressure ratio
drops below this value, then this permissive is satisfied.
There is a built-in hysteresis of 0.2.
Access
Main Menu >
Devices Menu
> HGV
Main Menu >
Devices Menu
> HGV button
> Setup
button.
Main Menu >
Devices Menu
> HGV button
> HGVs
button.
ARTC-SVX014A-EN