uses individual SP adjustable on the main
condenser valve screen.
PID direction. Rev – PID acts in Cooling mode; Fwd
– PID acts in Heating mode.
Valve Action. Dir – maximum PID signal
corresponds to valve fully opened state; Rev –
maximum PID signal corresponds to valve fully
closed state.
Access: Main Menu > Devices Menu > Cond >
Setup.
Condenser Fan Control
The chiller control system has two options for condenser
fan control as selected from the HMI configuration page –
HMI fan control:
Disabled – No condensing fan control from chiller
control system. This option is common in water-cooled
projects where condenser cooling is provided by
others.
ArcticCool Control – Requires T3C Companion
Controller. Preferred control methodology. This option
requires T3C Companion Controller. The T3C
Companion works with the Main Controller; they share
information including Inputs and Outputs. The
Companion cannot work as a stand-alone controller
because it does not have the inputs and outputs to
sustain the functionalities built-in. It is designed as a
companion relying on the main controller.
ARTC-SVX014A-EN
Operating Procedures
The Fan Control option of the T3C Companion
Controller has the following features:
Four independent circuits
Optimizes chiller operation based on ambient
temperature, running compressors speed or
wet bulb temperature
Optimizes chiller efficiency based on chiller load
Staging control for first two fan banks
Provides access to Free-Cooling Option (see
"Optional Functionalities," p.
The control page for this option has all the standard
features:
Figure 18. Fan control screen
Depending on SP mode selection Setup page
settings layout will look slightly different.
53).