Table 12. EXV control options
Screen
ARTC-SVX014A-EN
Controls
ArcticCool EXV Control.
•
This option requires ArcticCool T3C Companion
Controller. The T3C Companion works with the
ArcticCool Main Controller; they share
information including Inputs and Outputs. The
Companion cannot work as a stand-alone
controller because it does not have the inputs
and outputs to sustain the functionalities built in.
It is designed as a companion relying on the
Main Controller.
•
Five control modes:
–
Liquid Level High Pressure side – requires
Level sensor on the condenser.
–
Liquid Level Low Pressure side – requires
level sensor on the Evaporator.
–
Suction Superheat.
–
Discharge Superheat.
–
Sub-Cooling – Requires liquid line
temperature sensor.
•
Setpoint adjusts automatically based on chiller
capacity.
•
Capable of controlling up to four refrigeration
circuits.
ArcticCool EXV Setup Page.
•
PID Loop constants: P-Gain and Integral
•
Minimum Setpoint (for Sub-Cooling mode only).
•
Master Setpoint display:
–
Adjustable Setpoint for all the modes but
Sub-Cooling.
–
Maximum Setpoint (for Sub-Cooling mode
only).
EXV Common Parameters.
Circuit Common Parameters:
Max and Min operational valve values.
•
Start Position and Time
•
Sensor Failover Position
•
Low Lift Functions
Operating Procedures
Access
Main Menu > Devices Menu > EXV
Main Menu>Devices Menu> EXV>Setup
Main Menu>Devices Menu>EXV>Setup>Common
Parameters
37