■ Installing indoor unit on high ceiling
When an indoor unit is installed on a ceiling higher
than the standard height, make the high-ceiling setting
for fan speed adjustment.
Follow to the basic operation procedure
(
1
2
3
4
5
→
→
→
→
→
• For the CODE No. in Procedure
• Select the SET DATA for Procedure
"Height list of ceiling possible to be installed" table in
the following table.
▼ Height list of ceiling possible to be installed
Model
No. of discharge direction 4-way 3-way 2-way
Standard (Factory default)
3.9
High ceiling (1)
4.2
High ceiling (3)
4.5
6
).
3
, specify [5d].
4
from the
(Unit: mm)
High ceiling setup
SET DATA
4.2
4.5
0000
4.4
4.6
0001
4.6
–
0003
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. board.
The settings can also be changed with the switch on
the indoor microcomputer P.C. board.
* Once the setting is changed, setting to 0001 or
0003 is possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
SET DATA
0000
(Factory default)
0001
0003
To restore the factory defaults
To return the DIP switch settings to the factory
defaults, set SW501-1 and SW501-2 to OFF, connect
a separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
- 82 -
SW501-2
SW501-1
MCU(IC501)
SW501-1
SW501-2
OFF
OFF
ON
OFF
OFF
ON