9-1-7. How to set louver lock (Louver fix)
1
Push
(At the right side of the button)
for 4 seconds or more during stop of the
operation.
flashes
2
Push
(At the left side of the button)
and select the unit to be set.
• Every pushing the button, the unit No. changes.
UNIT No.
1–1
UNIT No.
The fan of the selected unit rotates and the louver
swings.
3
Push temp. set
No. of which air direction is to be fixed.
• The selected louver swings.
[F1]
[F2]
4
Push
direction of the louver of which swinging
you do not want.
Code
0001
0004
* If selecting above , and ..., there may be fear of
dewing in cooling time.
5
Push
to determine the setup contents.
• When the setup was determined,
on.
To set continuously the louver lock of the other
unit, repeat operations from 2 but from 3 to set
the other louver lock in the same unit,
respectively.
6
Push
to finish the setup.
0001 to 0005
(Louver fixed position code)
* F1 displayed at the item code on the remote
controller means that the 01 louver was selected
as shown in the figure
UNIT No.
UNIT No.
2–1
3–1
4–1
/
to display the louver
[F3]
[F4]
/
and select air
0002
0003
0005
mark goes
Louver
No.
Refrigerant pipe
Electric parts box
04
Drain pipe
NOTIFICATION
• Even if louver lock works, the louver temporarily
moves in the following cases.
1) During stop
2) During thermostat OFF
9-1-8. How to clear louver lock
In the item 4 of the louver lock setup procedure, set
the air direction to 0000.
mark goes off.
The operations from 1 to 3, 5
and 6 are same as those of the
louver lock.
9-1-9. How to set contents of save operation
1
Push
for 4 seconds or more during
stop of the operation.
flashes
2
Push
(At the left side of the button)
and select the unit to be set.
• Every pushing the button, the unit No. changes.
The fan of the selected unit rotates and the
louver swings.
UNIT No.
1–1
3
Determine the capacity restricted value when
pushing the save button of
• Every pushing the button, the capacity restricted
value can be set at 1% interval in the range
between 100% and 50%.
* The setting at shipment is 75%.
Setup value at saving
4
Push
and then push
- 80 -
03
02
01
Code 0000
UNIT No.
UNIT No.
2–1
3–1
UNIT No.
4–1
/
to finish the setup.
.