No.
Item
4
Air speed
selection
Outline of specifications
1) Operation with (HH), (H+), (H), (L+), (L) or [AUTO]
mode is carried out by the command from the remote
controller.
2) When the air speed mode [AUTO] is selected, the air
speed varies by the difference between Ta and Ts.
<COOL>
Ta (°C)
+3.0
HH
+2.5
(HH)
+2.0
H+ (HH)
+1.5
H (HH)
+1.0
L+ (H+)
+0.5
L (H)
Tsc
L (H)
–0.5
L (L+)
• Controlling operation in case when thermo of remote
controller works is same as a case when thermo of the
body works.
• If the air speed has been changed once, it is not
changed for 3 minutes. However when the air volume is
exchanged, the air speed changes.
• When cooling operation has started, select a downward
slope for the air speed, that is, the high position.
• If the temperature is just on the difference boundary, the
air speed does not change.
• Mode in the parentheses indicates one in automatic
cooling operation.
A
B
C
D
E
F
G
- 35 -
Remarks
HH > H+ > H > L+ >
L > UL