Acclimation; Performing The Safety Inspection Procedure; Rack Safety - IBM TS4300 User Manual

Tape library
Hide thumbs Also See for TS4300:
Table of Contents

Advertisement

Acclimation

Server and storage equipment (racks and frames) must be gradually acclimated to the surrounding
environment to prevent condensation.
When server and storage equipment (racks and frames) is shipped in a climate where the outside
temperature is below the dew point of the destination (indoor location), there is a possibility that water
condensation can form on the cooler inside and outside surfaces of the equipment when the equipment is
brought indoors.
Sufficient time must be allowed for the shipped equipment to gradually reach thermal equilibrium with
the indoor environment before you remove the shipping bag and energize the equipment. Follow these
guidelines to properly acclimate your equipment:
• Leave the system in the shipping bag. If the installation or staging environment allows it, leave the
product in the full package to minimize condensation on or within the equipment.
• Allow the packaged product to acclimate for 24 hours.
external or internal to the product) after 24 hours, acclimate the system without the shipping bag for an
additional 12 - 24 hours or until no visible condensation remains.
• Acclimate the product away from perforated tiles or other direct sources of forced air convection to
minimize excessive condensation on or within the equipment.
1
Unless otherwise stated by product-specific installation instructions.
Note: Condensation is a normal occurrence, especially when you ship equipment in cold-weather
®
climates. All IBM
these circumstances. When sufficient time is provided to allow the hardware to gradually acclimate to the
indoor environment, there should be no issues with long-term reliability of the product.

Performing the safety inspection procedure

Before you service the unit, complete the following safety inspection procedure.
1. Stop all activities between the host and the library's tape drives.
2. Turn off the power to the library by pushing in the Power button on the front of the tape library for 4
seconds.
3. Unplug the library's power cord from the electrical outlet and the library's power supply unit.
4. Check the library's power cords for damage, such as a pinched, cut, or frayed cord.
5. If drives are FC/SAS attached, check the tape drive's FC/SAS cable for damage.
6. Check the top and bottom covers of the library for sharp edges, damage, or alterations that expose its
internal parts.
7. Check the top and bottom covers of the library for proper fit. They must be in place and secure.
8. Check the product label at the rear of the library to make sure that it matches the voltage at your
outlet.

Rack safety

The following general safety information must be used for all rack-mounted devices.
DANGER
260  IBM TS4300 Tape Library Machine Type 3555: User's Guide
products are tested and verified to withstand condensation that is produced under